Document: LT0732 QE20 Fibre Networking User Manual
Issue 1.0 24 May 2023 Page 3-15
At the amp rack, SID 21, the Network and Remote SID setups are as followsnote
that to reach SID 20 for Speech and WIP the VoIP and WIP dial numbers for the
Fibre-Copper Bridge, SID 50, are used:
The configuration for the other amplifier rack, SID 22, is similar.
BGM and Paging Configuration.
The PIB at the MECP, SID 50, needs to have VoIP Proxy enabled on channels 3 and
4, with the URI mapped to lines 1 and 2 of the second ATA at the MECP, using a
G711u codec, so that BGM and paging audio can be streamed to the amp racks
SIDs 21 and 22.