8.5 Deployment as PROFIBUS DP slave
In the following the deployment of the PROFIBUS section as "intelli-
gent" DP slave on master system is described, which exclusively may
be configured in the Siemens SIMA
TIC Manager. The following steps
are required:
1. Configure a station with a CPU with operating mode DP slave.
2. Connect to PROFIBUS and configure the in-/output area for the
slave section.
3. Save and compile your project.
4. Configure another station with another CPU with operating
mode DP master
.
5. Connect to PROFIBUS and configure the in-/output ranges for
the master section.
6. Save, compile and transfer your project to your CPU.
1. Start the Siemens SIMATIC Manager and configure a CPU as
described at "Hardware configuration - CPU".
2. Designate the station as "...DP slave".
3. Add your modules according to the real hardware assembly.
4. Open the properties dialog of the DP interface of the CPU by
means of a double-click at ‘MPI/DP’ .
5. Set Interface type to "PROFIBUS".
6. Connect to PROFIBUS and preset an address (e.g. 3) and con-
firm with [OK].
7. Switch at Operating mode to "DP slave" .
8. V
ia Configuration you define the in-/output address area of the
slave CPU, which are to be assigned to the DP slave.
Fast introduction
Project engineering of
the slave section
VIPA System 300S Deployment PROFIBUS communication
Deployment as PROFIBUS DP slave
HB140 | CPU | 314-6CF03 | GB | 16-43 197