6.8.2 CAN BUS NODE ID SETTING
The node IDs for the CAN bus are set using two rotary buttons under the service cover.
The node IDs can be set between 1 and 100 as follows:
Node ID = 10 x value of rotary button on left + value of rotary button on right
Examples:
Node ID 01 (0/1)
Node ID 23 (2/3)
The node ID is only read in and calculated when the control unit is switched on (powered
up). For a change to the node ID to take e ect, the control unit must be switched o and
on again.
Exception:
Node ID 100 (0/0)