First Time Power-Up and Start-Up
5
5-4 | CFW-11
The use of the Oriented Start-up routine for setting the inverter parameters may lead to the automatic modification
of other internal parameters and/or variables of the inverter.
During the Oriented Start-up routine, the message "Config" will be displayed at the left top corner of the keypad.
Step Action/Result Display indication Step Action/Result Display indication
1 - Monitoring mode
- Press "Menu" (right soft key)
Ready
LOC
0rpm
13:48 Menu
0 rpm
0.0 A
0.0 Hz
2 - Group "00 ALL
PARAMETERS" has been
already selected
Ready
LOC
0rpm
Return 13:48 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
3 - Group "01 PARAMETER
GROUPS" is selected
Ready
LOC
0rpm
Return 13:48 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
4 - Group "02 ORIENTED
START-UP" is then selected
- Press "Select"
Ready
LOC
0rpm
Return 13:48 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
5 - Parameter "Oriented Start-
Up P0317: No" has been
already selected
- Press "Select"
Ready
LOC
0rpm
Return 13:48 Select
Oriented Start-Up
P0317: No
6 - The value of
"P0317 = [000] No" is
displayed
Ready
LOC
0rpm
Return 13:48 Save
P0317
Oriented Start-up
[000] No
7 - The parameter value is
modified to "P0317 = [001]
Yes"
- Press "Save"
Ready
LOC
0rpm
Return 13:48 Save
P0317
Oriented Start-up
[001] Yes
8 - At this point the Oriented
Start-up routine starts and the
"Config" status is displayed
at the top left corner of the
keypad
- The parameter "Language
P0201: English" is already
selected
- If needed, change the
language by pressing "Select".
Then, press
or
to scroll through the
available options and press
"Save" to select a different
language
Config
LOC
0rpm
Reset 13:48 Select
Language
P0201: English
Type of Control
P0202: V/F 60 HZ
9 - If needed, change the value
of P0202 according to the
type of control. To do so, press
"Select"
- The settings listed here are
valid only for P0202 = 0
(V/f 60 Hz) or P0202 = 1
(V/f 50 Hz). For other options
(Adjustable V/f, VVW, or
Vector modes), please refer to
the programming manual
Config
LOC
0rpm
Reset 13:48 Select
Language
P0201: English
Type of Control
P0202: V/F 60 HZ
10 - If needed, change the value
of P0296 according to the line
rated voltage
To do so, press "Select"
This modification will affect
P0151, P0153, P0185, P0321,
P0322, P0323, and P0400
Config
LOC
0rpm
Reset 13:48 Select
Type of Control
P0202: V/F 50 HZ
Line Rated Voltage
P0296: 500 - 525 V
11 - If needed, change the value of
P0298 according to the inverter
application. To do so, press
"Select". This modification will
affect P0156, P0157, P0158,
P0401, P0404 and P0410 (this
last one only if P0202 = 0, 1,
or 2 - V/f control). The time
and the activation level of the
overload protection will be
affected as well
Config
LOC
0rpm
Reset 13:48 Select
Line Rated Voltage
P0296: 500 - 525 V
Application
P0298: Heavy Duty
12 - If needed, change the
value of P0398 according
to the motor service factor
To do so, press "Select"
This modification will affect
the current value and the
activation time of the motor
overload function
Config
LOC
0rpm
Reset 13:48 Select
Application
P0298: Heavy Duty
Motor Service Factor
P0398: 1.15