Option Kits and Accessories
7
7-4 | CFW-11
WEG Part
Number
Name Description Slot
Identication
Parameters
P0027 P0028
11417559 KN1G-01 Nema1 kit for the frame size G - - -
11010264 KIP21D-01 IP21 kit for frame size D (standard for option 21) - - -
11337710 KME-01 Frame size E movement kit - - -
11337634 KMF-01 Frame size F movement kit - - -
11337714 KMG-01 Frame size G movement kit - - -
10794631 DBW030250
D5069SZ
Dynamic braking module DBW03 - - -
13166838 DBW040250
D5069SZ
Dynamic braking module DBW04 - - -
(1) Refer to the PLC module manual.
(2) Refer to the Anybus-CC communication manual.
(3) Refer to the programming manual.
(4) Use DB-9 pin, male-to-female, straight-through cable (serial mouse extension type) for connecting the keypad to the inverter or Null-Modem standard
cable. Maximum cable length: 10 m (33 ft).
Examples:
- Mouse extension cable - 1.80 m (6 ft); Manufacturer: Clone.
- Belkin pro series DB9 serial extension cable 5 m (17 ft); Manufacturer: Belkin.
- Cables Unlimited PCM195006 cable, 6 ft DB9 m/f; Manufacturer: Cables Unlimited.
(5) For more details see Section 8.6 NEMA 1 KITs on page 8-16.
(6) The MMF-03 module has a reserved space for the user (for example: write the application software version SoftPLC).
7.2.1 Use of External Dynamic Braking Module DBW03 and DBW04
The dynamic braking module can be added externaly to any model, and particularly to frame sizes F, G and
H, which do not have built-in braking IGBT.
This module is connected to the DC link terminals and the braking resistor must be connected to the braking
module terminals.
See electrical diagram example for the frame sizes F, G and H in Figure 3.24 on page 3-32 and Figure 3.25
on page 3-34.
See also DBW03 and DBW04 instructions manual for detailed information.
For frame sizes F and G it's recommended to use DBW03 model.
For frame size H it's recommended to use DBW04 model.
NOTE!
Dynamic braking in models from frame sizes F, G and H:
- For accessing the DC link connections it's necessary to remove top cover. See Figure 3.31 on page
3-39.
- The maximum rms braking currents on DC link terminals of standard models in frame sizes F, G
and H are the following:
Frame size F: 143 Amps-rms
Frame size G: 216 Amps-rms
Frame size H: rated DC current according Table 8.2 on page 8-3 and Table 8.4 on page 8-5.