First Time Power-Up and Start-Up
5
CFW-11 | 5-3
5.2.1 Password Setting in P0000
Step Action/Result Display indication
1 - Monitoring mode
- Press "Menu"
(rigth soft key)
Ready
LOC
0rpm
15:45 Menu
0 rpm
0.0 A
0.0 Hz
2 - Group "00 ALL
PARAMETERS" is already
selected
- Press "Select"
Ready
LOC
0rpm
Return 15:45 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
3 - Parameter "Access to
Parameters P0000: 0" is
already selected
- Press "Select"
Ready
LOC
0rpm
Return 15:45 Select
Access to Parameters
P0000: 0
Speed Reference
P0001: 90 rpm
4 - To set the password, press
the Up Arrow
until
number 5 is displayed in the
keypad
Ready
LOC
0rpm
Return 15:45 Save
P0000
Access to Parameters
0
5 - When number 5 is displayed
in the keypad, press "Save"
Ready
LOC
0rpm
Return 15:45 Save
P0000
Access to Parameters
5
6 - If the setting has been
properly performed, the
keypad should display "Access
to Parameters P0000: 5"
- Press "Return"
(left soft key)
Ready
LOC
0rpm
Return 15:45 Select
Access to Parameters
P0000: 5
Speed Reference
P0001: 90 rpm
7 - Press "Return"
Ready
LOC
0rpm
Return 15:45 Select
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
8 - The display returns to the
monitoring mode
Ready
LOC
0rpm
15:45 Menu
0 rpm
0.0 A
0.0 Hz
Figure 5.1 - Steps for allowing parameters modication via P0000
5.2.2 Oriented Start-Up
There is a group of parameters named "Oriented Start-up" that makes the inverter settings easier. Inside this
group, there is a parameter - P0317 - that shall be set to enter into the Oriented Start-up routine.
The Oriented Start-up routine allows you to quickly set up the inverter for operation with the line and motor
used. This routine prompts you for the most commonly used parameters in a logic sequence.
In order to enter into the Oriented Start-up routine, follow the steps presented in Figure 5.2 on page 5-5, first
modifying parameter P0317 to 1 and then, setting all remaining parameters as they are prompted in the display.