EasyManua.ls Logo

WEG CFW-11 Series - Emission and Immunity Levels

WEG CFW-11 Series
145 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Connection
3
3-64 | CFW-11
3.4.3 Emission and Immunity Levels
Table 3.19 - Emission and immunity levels
EMC Phenomenon Basic Standard Level
Emission:
Mains terminal disturbance voltage
Frequency range: 150 kHz to 30 MHz
IEC/EN61800-3 (2004) +
A1 (2011)
It depends on the inverter model and on the motor cable
lenght. Refer to Table 3.20 on page 3-65
Electromagnetic radiation disturbance
Frequency range: 30 MHz to 1000 MHz
Immunity:
Electrostatic discharge (ESD) IEC 61000-4-2 (2008) 4 kV for contact discharge and 8 kV for air discharge
Fast transient-Burst IEC 61000-4-4 (2012) 2 kV / 5 kHz (coupling capacitor) power input cables
1 kV / 5 kHz control cables, and remote keypad cables
2 kV / 5 kHz (coupling capacitor) motor output cables
Conducted radio-frequency common mode IEC 61000-4-6 (2013) 0.15 to 80 MHz; 10 V; 80 % AM (1 kHz)
Motor cables, control cables, and remote keypad cables
Surge immunity IEC 61000-4-5 (2014)
1.2/50 µs, 8/20 µs
1 kV line-to-line coupling
2 kV line-to-ground coupling
Radio-frequency electromagnetic field IEC 61000-4-3 (2010) 80 MHz to 1000 GHz
10 V/m
1,4 GHz to 2 GHz
3 V/m
2 GHz to 2,7 GHz
1 V/m
80 % AM (1 kHz)

Table of Contents

Other manuals for WEG CFW-11 Series

Related product manuals