Installation and Connection
3
3-8 | CFW-11
Mounting surface opening dimensions and position/diameter of the mounting holes, as shown in Figure 3.2
on page 3-4.
Frame Sizes F, G and H:
ATTENTION!
The part of the inverter that stays outside the cabinet is rated IP20.
The power specified in Table 8.1 on page 8-2 to Table 8.4 on page 8-5 under "Dissipated power in
Watts - flange mounting" will be dissipated inside the cabinet. Use Table 8.1 on page 8-2 and Table 8.3
on page 8-4 for inverters with AC power supply and Table 8.2 on page 8-3 and Table 8.4 on page
8-5 for inverters with DC power supply. The other losses (power modules) will be dissipated at the external
ventilation duct.
The inverter mounting supports and the hoisting eyes must be removed. Refer to the Figure 3.8 on page
3-11, positions I and J.
Dimensions of the flange-mounting opening and the diameters of the securing holes must be according to
the Figure 3.2 on page 3-4.
Table 3.1 - Minimum required cabinet cooling air ow
Frame Size CFM I/s m³/min
B 42 20 1.2
C 96 45 2.7
D 132 62 3.7
E 265 125 7.5
F 460 217 13
G 680 321 19.3
H 1100 520 31.2