EasyManua.ls Logo

WEG CFW-11 Series - Page 76

WEG CFW-11 Series
145 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Connection
3
3-46 | CFW-11
CCW
CW
≥5 kΩ
rpm
amp
XC1
Terminal Strip
Factory Setting Function Specications
1 REF+ Positive reference for
potentiometer
Output voltage: +5.4 V, ±5 %
Maximum output current: 2 mA
2 AI1+ Analog input # 1:
speed reference (remote)
Differential
Resolution: 12 bits
Signal: 0 to 10 V (R
IN
= 400 kΩ) / 0 to 20 mA / 4 to 20 mA (R
IN
= 500 Ω)
Maximum voltage: ±30 V
3 AI1-
4 REF- Negative reference for
potentiometer
Output voltage: -4.7 V, ±5 %
Maximum output current: 2 mA
5 AI2+ Analog input # 2:
no function
Differential
Resolution: 11 bits + signal
Signal: 0 to ±10 V (R
IN
= 400 kΩ) / 0 to 20 mA / 4 to 20 mA (R
IN
= 500 Ω)
Maximum voltage: ±30 V
6 AI2-
7 AO1 Analog output # 1:
speed
Galvanic isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
L
≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (R
L
≤ 500 Ω)
Protected against short-circuit
8 AGND
(24 V)
Reference (0 V) for the
analog outputs
Connected to the ground (frame) through an impedance: 940 Ω resistor in
parallel with a 22 nF capacitor. Same reference as the one of DGND *
9 AO2 Analog output # 2:
motor current
Galvanic isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
L
≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (R
L
≤ 500 Ω)
Protected against short-circuit
10 AGND
(24 V)
Reference (0 V) for the
analog outputs
Connected to the ground (frame) through an impedance: 940 Ω resistor in
parallel with a 22 nF capacitor. Same reference as the one of DGND *
11 DGND* Reference (0 V) for the 24 Vdc
power supply
Connected to the ground (frame) through an impedance: 940 Ω resistor in
parallel with a 22 nF capacitor. Same reference as the one of AGND (24 V)
12 COM Common point of the digital
inputs
13 24 Vdc 24 Vdc power supply 24 Vdc power supply, ±8 %
Capacity: 500 mA
Note: in the models with the 24 Vdc external control power supply
(CFW11...O...W...) the terminal 13 of XC1 becomes an input, i.e., the user
must connect a 24 Vdc power supply for the inverter (refer to the Item 7.1.3
24 Vdc External Control Power Supply on page 7-1, for more details). In
all the other models this terminal is an output, i.e., the user has a 24 Vdc
power supply available there
14 COM Common point of the digital
inputs
15 DI1 Digital input # 1:
Start/Stop
6 isolated digital inputs
High level ≥ 18 V
Low level ≤ 3 V
Maximum input voltage = 30 V
Input current: 11 mA @ 24 Vdc
16 DI2 Digital input # 2:
direction of rotation (remote)
17 DI3 Digital input # 3:
no function
18 DI4 Digital input # 4:
no function
19 DI5 Digital input # 5:
Jog (remote)
20 DI6 Digital input # 6:
2
nd
ramp
21 NC1 Digital output #1 DO1 (RL1):
no fault
Contact rating:
Maximum voltage: 240 Vac
Maximum current: 1 A
NC - normally closed contact
C - common
NO - normally open contact
22 C1
23 NO1
24 NC2 Digital output #2 DO2 (RL2):
N > N
X
- speed > P0288
25 C2
26 NO2
27 NC3 Digital output #3 DO3 (RL3):
N* > N
X
- speed reference
> P0288
28 C3
29 NO3
(a) Digital inputs working as "Active High"