14
APPLICATIONS
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
P925 - Time for Low Level Fault for the Control Process Variable
Range: 0.0 to 999.9 s
Description:
This parameter defines how long the low level alarm condition should remain so that the control process variable
(A760) will generate fault “F761: Low Level Fault of the Control Process Variable”.
NOTE!
Setting it to ”0.0 s” disables the low level fault for the control process variable.
P926 - Value for High Level Alarm for the Control Process Variable
Range: -99.99 to 99.99
Description:
This parameter defines the value above which the high level alarm will be generated for the control process variable
(A762).
NOTE!
Setting it to ”0” disables the high level alarm and fault for the control process variable.
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
P927 - Time for High Level Fault for the Control Process Variable
Range: 0.0 to 999.9 s
Description:
This parameter defines how long the high level alarm condition should remain so that the control process variable
(A762) will generate fault “F763: High Level Fault of the Control Process Variable”.
NOTE!
Setting it to ”0.0 s” disables the high level fault for the control process variable.
P928 - Selection of the PID Controller Control Action
Range: 0 = Disable PID Controller
1 = Enable PID Controller in Direct Mode
2 = Enable PID Controller in Reverse Mode
Properties: cfg
Description:
Micro Mini Drives | 14-11