102 WILO SE 2018-12
Holding register
(Protocol)
Name Data type Scale & unit Elements Access Added
40015
(14)
Drives on/off BOOL RW 31.000
40025
(24)
Control mode ENUM 0. p-c
1. dp-c
2. dp-v
3. dT-c
4. dT-v
5. n(TV)
6. n(TR)
7. n(TP)
8. n(TA)
9. n-c
10. fill
11. empty/drain
12. FTS
13. cleans/day
14. cleans/
month
R 31.000
40026
(25)
Current value INT16 0.1 bar
0.1 m
0.1 K
0.1 °C
1 cm
1 min
0.1 h
0.1 psi
R 31.000
40041
(40)
Pump 1 mode ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40042
(41)
Pump 2 mode ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40043
(42)
Pump 3 mode ENUM 0. Off
1. Hand
2. Auto
RW 31.000
40062
(61)
Switch box state BITMAP 0: SBM
1: SSM
R 31.000
40139 - 40140
(138-139)
Error state BITMAP32 0: Sensor error
1: P man
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
8: Pump 4 Alarm
9: Pump 5 Alarm
10: Pump 6
Alarm
11: -
12: -
13: Frost
14: Battery Low
15: High water
16: Priority off
17: Redundancy
18: Plausibility
19: Slave com-
munication
20: Net supply
21: Leakage
R 31.000