en Commissioning
82 WILO SE 2018-12
Fig.41: Menu 5.43
Menu no. 5.43
Description “Pump kick running time”
Value range 0 … 60s
Factory setting 5s
Fig.42: Menu 5.44
Menu no. 5.44
Description Activation delay after power failure
Value range 0 … 180s
Factory setting 3s
Fig.43: Menu 5.50
Menu no. 5.50
Description Dry-running level (drain)/ min. water level (fill)
Value range 0 … 12.5m
Factory setting 0.15m
Explanation
If the level is monitored with a separate float switch, deac-
tivate the level sensor: Enter the value “0.00m”.
Fig.44: Menu 5.51
Menu no. 5.51
Description High water level
Value range 0 … 12.5m
Factory setting 0.46m
Fig.45: Menu 5.57
Menu no. 5.57
Description Max. running time per pump
Value range 0 … 60min
Factory setting 0min
Explanation
Maximum permissible running time of a pump. Once the
time has been exceeded, the system switches to the next
pump. After three change cycles, the collective fault signal
(SSM) is activated.
The setting “0min” switches the running time monitoring
off.
Fig.46: Menu 5.58
Menu no. 5.58
Description Collective run signal (SBM) function
Value range on, run
Factory setting run
Explanation
“on”: Switchgear ready for operation
“Run”: At least one pump is running.