en Commissioning
82 WILO SE 2018-12
Fig.41: Menu 5.43
Menu no. 5.43
Description “Pump kick running time”
Value range 0 … 60s
Factory setting 5s
Fig.42: Menu 5.44
Menu no. 5.44
Description Activation delay after power failure
Value range 0 … 180s
Factory setting 3s
Fig.43: Menu 5.50
Menu no. 5.50
Description Dry-running level (drain)/ min. water level (fill)
Value range 0 … 12.5m
Factory setting 0.15m
Explanation
If the level is monitored with a separate float switch, deac-
tivate the level sensor: Enter the value “0.00m”.
Fig.44: Menu 5.51
Menu no. 5.51
Description High water level
Value range 0 … 12.5m
Factory setting 0.46m
Fig.45: Menu 5.57
Menu no. 5.57
Description Max. running time per pump
Value range 0 … 60min
Factory setting 0min
Explanation
Maximum permissible running time of a pump. Once the
time has been exceeded, the system switches to the next
pump. After three change cycles, the collective fault signal
(SSM) is activated.
The setting “0min” switches the running time monitoring
off.
Fig.46: Menu 5.58
Menu no. 5.58
Description Collective run signal (SBM) function
Value range on, run
Factory setting run
Explanation
“on”: Switchgear ready for operation
“Run”: At least one pump is running.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Wilo Wilo-Control EC-L and is the answer not in the manual?

Wilo Wilo-Control EC-L Specifications

General IconGeneral
BrandWilo
ModelWilo-Control EC-L
CategoryControl Unit
LanguageEnglish

Related product manuals