Manual 26815 QuickTrip Electro-Hydraulic Trip Block Assembly
Woodward 8
The Temperature Code T4 (135 °C) may be exceeded if QuickTrip is cycled on and off at a frequency
exceeding 1 Hz. This is considered a rare malfunction and not part of the intended use of the device.
Connect external safety ground terminal to earth ground.
For installation using Ex nA nC protection:
1. Transient protection of QuickTrip is to be provided externally by the end user. The transient protection
device is to be set at a level not exceeding 140% of the peak rated voltage.
2. The installation of QuickTrip shall only be within a Pollution Degree 2 environment as defined in IEC
60664-1.
3. Minimum ambient temperature shall not be lower than -20 °C
Compliance with the Machinery Directive 2006/42/EC noise measurement and mitigation requirements is
the responsibility of the manufacturer of the machinery into which this product is incorporated.
Do not connect/disconnect/substitute components
WARNING - Explosion Hazard—Do not remove covers or
connect/disconnect electrical connectors unless power has
been switched off or the area is known to be non-hazardous.
Substitution of components may impair suitability for Class
I, Division 2 or Zone 2 applications.
AVERTISSEMENT - Risque d’explosion— Ne pas enlever les
couvercles, ni raccorder / débrancher les prises électriques,
sans vous en assurez auparavant que le système a bien été
mis hors tension; ou que vous situez bien dans une zone
non explosive.
La substitution de composants peut rendre ce matériel
inacceptable pour les emplacements de Classe I,
applications Division 2 ou Zone 2.