EasyManua.ls Logo

Worcester GB162-100

Worcester GB162-100
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
6720813171 (2015/04)32
Fig. 66 EMS bus polarity
Installing and connecting function modules outside the boiler
Install the module on the wall.
Make a sufficiently long EMS bus connection cable, using a 2-core
cable of 0.4 - 0.75 mm² and the connector enclosed with the module
( fig. 66). Important: Use the connector of the same colour as the
connections on the module.
Connect the EMS bus connection cable to the orange connection of
the terminal strip [1].
Fig. 67 Terminal strip - Room controller RC and EMS bus (connection
colour orange)
Connect the other end of the EMS bus connection cable to the first
module ( fig. 65).
If more modules are used, the EMS bus connection for the second
module may be branched off from the first module using the cable
enclosed with the module.
Connect the EMS bus connection lead of the first module to the next
module ( fig. 65).
Make a sufficiently long 230 VAC mains cable, using a 3-core cable of
at least 0.75 mm² with an earthing wire, the connector enclosed with
the module and a 230 VAC earthed plug.
Connect the 230 VAC mains cable to the module ( fig. 65). If more
modules are used, the 230 VAC supply to the next module can be
branched off from the previous module using the connector enclosed
with the module and a 3-core 0.75-mm² current cable with an
earthing wire.
Connect the 230 VAC supply cable of the previous module to the
next module ( fig. 65).
9Operation
9.1 General items
The boiler is fitted with a control unit, the BC10 basic controller.
This controller can be used to control the heating system.
Push on the control panel to open it.
Fig. 68 Opening the control panel
The BC10 basic controller is located on the left, behind the door
( fig. 1, [4]).
The BC10 basic controller consists of the following components:
Fig. 69 BC10 basic controller
[1] Mains switch
[2] “Reset” button
[3] “Chimney sweep” button
[4] “Service button”
[5] Service Connector
[6] “Burner” LED (On/Off)
[7] “Heat demand” LED
[8] Maximum CH flow temperature dial
[9] Display
[10] DHW temperature dial
[11] “DHW mode” LED
Mains switch
The mains switch [1] is used to switch the boiler on and off.
“Reset” button
If a fault has occurred you may have to restart the boiler by pressing the
“Reset” button [2]. This is only required in the event of a “locking” fault.
“Blocking” faults are reset automatically as soon as their cause has been
corrected. The display shows [\/r/e| during the reset operation.
NOTICE:
Pay attention to the polarity when using an EMS bus
connection cable.
Connect the wire from terminal 1 to terminal 1 and
from terminal 2 to terminal 2 ( fig. 65 and 66).
The module may have the letters RC or EMS above the
connection ( fig. 65, [1]).
6 720 648 726-066.1TD
RC
6 720 648 726-067.1TD
1
If the boiler stops due to a fault again after resetting the
fault, the fault can be remedied using the Service
instructions. Contact Worcester if necessary.
See the back of this document for contact details.
6 720 648 726-044.1TD
888
1
10
9
8
7
6
5432
1
6 720 648 726-069.1TD
11

Table of Contents

Other manuals for Worcester GB162-100

Related product manuals