EasyManua.ls Logo

Worcester GB162-100

Worcester GB162-100
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
6720813171 (2015/04)48
12.12 Inspection log book
Enter your signature and the date after completing the inspection activities.
13 Maintenance
Prepare the system for maintenance as described in the chapter on
Inspection ( section 12.1, page 46).
13.1 Removing the boiler door
If the boiler door cannot be fully opened, it may be necessary to remove
the door for inspection and maintenance activities.
Proceed as follows:
Unscrew the control panel from the boiler door and hang it on the
boiler frame ( fig. 119 “Undoing the screws”, page 53).
Unscrew the bolt from the left-hand top hinge of the boiler door and
remove it together with the washer.
Slightly lift the door and pull it from the hinge. Put the door upright in
a safe position and make sure that it cannot fall over.
Fig. 103 Removing the boiler door
Inspection activities Date: ________ Date: ________ Date: ________
1. Checking the general condition of the heating system. 
2. Carrying out a visual inspection and function test of
the heating system.

3. Checking the gas and water-bearing system
components for:
Operational tightness
Visible corrosion
Signs of wear.
Section 10.2.8, page 42.
Section 12.3, page 47.

4. Measuring the ionisation current. Section 10.2.11, page 43. ___________ μA ___________ μA ___________ μA
5. Measuring the gas supply pressure (working
pressure).
Section 10.2.6, page 40. ________ mbar ________ mbar ________ mbar
6. Checking the gas/air-ratio. Section 10.2.7, page 40. _________ Pa _________ Pa _________ Pa
7. Carrying out a tightness check of the gas circuit in
operating conditions.
Section 10.2.8, page 42. 
8. Measuring the carbon monoxide content (CO), air
free.
Section 10.2.9, page 43. _________ ppm _________ ppm _________ ppm
9. Checking the system pressure.
Pre-pressure of expansion vessel (also see
installation instructions for expansion vessel)
•Filling pressure.
Section 10.1, page 37.
_________ bar
_________ bar
_________ bar
_________ bar
_________ bar
_________ bar
10. Checking the operation and safety of the air intake and
flue gas pipe.
Section 10.2.4, page 40. 
11. Checking the boiler settings of the control device (in
accordance with requirements).
See the documents for the
control device.

12. Final check of the inspection activities, documenting
the measurement and test results.

13. Confirming proper inspection.
Company stamp/
signature/date
Company stamp/
signature/date
Company stamp/
signature/date
Table 20
The cover over the electrical connections does not have
to be removed from the boiler.
6 720 648 726-104.1TD

Table of Contents

Other manuals for Worcester GB162-100

Related product manuals