EasyManuals Logo

Worcester GB162-100 Installation And Servicing Instructions

Worcester GB162-100
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
Commissioning
6720813171 (2015/04) 41
Press and hold the “Chimney sweep” button [3] (approximately 2
seconds), until the dot in the right-hand bottom corner of the display
[9] appears. See also table 10, “Flue gas test”, page 34.
After the “Burner” LED [6] has lit up wait for one minute until the
boiler is burning at full load.
Measure the gas supply pressure and enter it in the commissioning
log book, page 72.
The gas supply pressure must be:
for natural gas H min. 17 mbar, max. 25 mbar, nominal supply
pressure 20 mbar.
for LPG min. 30 mbar, max. 50 mbar, nominal supply pressure
37 mbar.
Press the “Service” button [4] repeatedly until the temperature
reading is shown in the display.
Press the “Chimney sweep” button [3] to clear the reading. Also see
table 10, “Flue gas test”, page 50.
Fig. 86 BC10 basic controller
Close the gas valve ( fig. 81, page 39).
Remove the gauge-connection tube and tighten the screw plug on the
testing nipple again.
Open the gas valve again by pushing on the gas valve and turning it ¼
rotation in an anticlockwise direction ( fig. 79, page 39).
10.2.7 Checking and adjusting the gas/air-ratio
Open at least 2 thermostatic radiator valves. Do not switch on the
boiler.
Push on the control panel to open it ( fig. 68, page 32).
Switch off the heating system by pressing the mains switch of the
BC10 basic controller ( fig. 86, [1]).
Close the gas valve ( fig. 81, page 39).
Turn the vent key through a quarter rotation to undo the boiler door
lock ( fig. 71, see detailed picture, page 37).
Push the fastener down and open the boiler door ( fig. 71,
page 37).
Open the screw plug on the testing nipple for the burner pressure by
2 turns [1].
Set the pressure gauge to “0”.
Fig. 87 Checking the gas/air ratio
Use a connection tube to connect the positive port of the pressure
gauge to the testing nipple for burner pressure ( fig. 87, [2]).
Slowly open the gas valve by pushing on the gas valve and turning it
¼ rotation in an anticlockwise direction ( fig. 79, page 39).
Switch on the heating system by pressing the mains switch of the
BC10 basic controller ( fig. 86, [1]).
Activate the Service mode in accordance with the “Service mode”
menu ( table 11, page 34).
DANGER: Danger of fatal accident from explosive
fumes.
Check the testing nipples used for leaks.
Only use approved leak detection spray to locate
leaks.
NOTICE:
Check the gas supply pipe or contact the relevant gas
utility company if the required supply pressure is not
available.
If the supply pressure is too high, a gas pressure
regulator must be integrated upstream of the gas
fitting. Contact the gas utility company.
WARNING:
Damage to the boiler by incorrect adjustment of the gas/
air-ratio.
Adjust gas/air-ratio only with part load.
Adjust gas/air-ratio only based on the gas/air
pressure differential and never based on measured
flue gas values such as CO/CO
2
/NO
x
.
888
1
10
9
8
7
6
5432
1
6 720 648 726-069.1TD
11
Throughout the measuring operation, keep the digital
pressure gauge in the same position (horizontal or
vertical) in which it was reset to “0”.
GB162-50/65
GB162-80/100
6720813171-2.1TD

Table of Contents

Other manuals for Worcester GB162-100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Worcester GB162-100 and is the answer not in the manual?

Worcester GB162-100 Specifications

General IconGeneral
BrandWorcester
ModelGB162-100
CategoryBoiler
LanguageEnglish

Related product manuals