EasyManua.ls Logo

Worcester GB162-100

Worcester GB162-100
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
6720813171 (2015/04)42
Set the capacity to minimum (part load) according to the “Service
mode” menu ( table 11, page 34).
After the “Burner” LED ( fig. 86, [6]) has lit up wait for one minute
until the boiler is burning at part load.
Read the differential pressure during service mode. The differential
pressure (p
gas
- p
air
) must be –5 Pa (±5 Pa) (indication on the
pressure gauge: –10 to 0 Pa).
Fig. 88 Gas/air difference at low load
Enter the result in the commissioning log book ( section 10.5
“Commissioning record log book”, page 45).
If the gas/air-ratio is incorrect, it must be adjusted on the set screw
(Torx 40 H) [1]. The set screw is located behind the screw-on cover.
Fig. 89 Gas/air difference at low load
Press the “Chimney sweep” button ( fig. 86, [3]) until the dot
disappears from the display.
Switch off the heating system by pressing the mains switch of the
BC10 basic controller ( fig. 90, [1]).
Close the gas valve ( fig. 81, page 39).
Remove the measuring devices.
Tighten the screw in the burner pressure measuring nipple.
Slowly open the gas valve by pushing on the gas valve and turning it
¼ rotation in an anticlockwise direction ( fig. 79, page 39).
Switch on the heating system by pressing the mains switch of the
BC10 basic controller ( fig. 90, [1]).
Press and hold the “Chimney sweep” button ( fig. 90, [3])
(approximately 2 seconds), until the dot in the right-hand bottom
corner of the display ( fig. 90, [9]) appears. See also table 10,
“Flue gas test”, page 34.
After the “Burner” LED ( fig. 90, [6]) has lit up wait for one minute
until the boiler is burning at full load.
Press the “Chimney sweep” button ( fig. 90, [3]) to clear the
reading. See also table 10, “Flue gas test”, page 34.
Check that the boiler performance is still at the required value. See
table 13 “Settings”, page 36.
10.2.8 Carrying out a leakage test in operating conditions
Press and hold the “Chimney sweep” button [3] (approximately 2
seconds), until the dot in the right-hand bottom corner of the display
[9] appears. See also table 10, “Flue gas test”, page 34.
After the “Burner” LED [6] has lit up wait for one minute until the
boiler is burning at full load.
Use a foaming product to check all sealing locations in the total gas
circuit of the burner while the burner is active.
Press the “Chimney sweep” button [3] to clear the reading. See also
table 10, “Flue gas test”, page 34.
Fig. 90 BC10 basic controller
-15 -10 -5 0 5 (Pa)
-0.15 -0.10 -0.05 0.00 0.05 (mbar)
turn anticlockwise turn clockwise
wrong right wrong
6 720 648 726-088.1TD
6 720 648 726-089.1TD
1
DANGER: Danger of fatal accident from explosive
fumes.
Check the testing nipples used for gas tightness.
Only use approved leak detection products to locate
leaks.
WARNING:
Damage to the installation due to short circuits.
Cover any hazardous locations prior to locating the
leaks.
Do not spray the leak detection product on cable
runs, plugs or electrical wiring. Do not let it drip onto
them either.
DANGER: Danger of fatal accident from explosive
fumes.
Pipes and fittings may leak after commissioning
activities have been carried out.
Only use approved leak detection products to locate
leaks.
WARNING:
Damage to the installation due to short circuits.
Cover any hazardous locations prior to locating the
leaks.
Do not spray the leak detection product on cable
runs, plugs or electrical wiring. Do not let it drip onto
them either.
888
1
10
9
8
7
6
5432
1
6 720 648 726-069.1TD
11

Table of Contents

Other manuals for Worcester GB162-100

Related product manuals