7 181 465 347 (01.07)36
Rectifying faults
4.5 Faults that are not displayed
4.5.1 Appliance faults
Boiler indicates P1, P2, P3 at start-up and then restarts with P1..
Check Action
1. Fuse T 1.6 A (312) defective. yes: B Turn ON the appliance.
B Change the fuse.
B Power OFF the appliance.
Start sequence not completed? 2.
no: 2.
2. The PCB control board is damaged. B Change PCB control board.
Excessive burner noise, rumbling noises
Check Action
1. Does the gas supply type match the
specifications on the appliance iden-
tification plate?
yes: 2.
no: B Convert appliance to correct gas type
1)
.
2. B Test gas supply pressure - OK?
1)
? yes: 3.
no: B Decommission appliance.
B Notify gas company.
3. Problem with flue?
B Check CO
2
level in combustion
air.
> 0,2 % CO
2
?
yes: B Check flue and repair or replace if necessary.
no: 4.
4. B Remove silencer, flue pipe and
mixer unit.
Is internal flue pipe/silencer dirty or
clogged or are seals defective or
incorrectly fitted?
yes: B Repair or replace components.
B Grease seal before fitting,
B Make sure it is fitted in correct position.
no: 5.
5. Flue gas CO
2
levels measured at
min. and max. load do not match
specified levels
1)
.
B Measure CO
2
levels.
yes: B Adjust CO
2
levels.
no: B Power OFF the appliance.
B Change the gas valve.
B Turn ON the appliance.
1) See installation instructions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Worcester GREENSTAR HE combi Series and is the answer not in the manual?

Worcester GREENSTAR HE combi Series Specifications

General IconGeneral
BrandWorcester
ModelGREENSTAR HE combi Series
CategoryBoiler
LanguageEnglish

Related product manuals