EasyManuals Logo

Xtrails Heitel ipVG User Manual

Xtrails Heitel ipVG
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
ipVG Product Guide HeiTel by Xtralis
62 29794_00
IPCamera
For all cameras:
Manufacturer = Off; Model = not selected; IP adrress = not defined;
Generic "GET" command 1 = not defined;
Generic "GET" command 2 = not defined
13.1 Interface Specifications RS-232/485
The table below contains an overview of the most important features of interfaces RS-232 and RS-485
interfaces:
Function RS-232 / V.24 RS-485
Transmission type asymmetrical symmetrical
Minimum number of wires Unidirectional 2,
(bidirectional 3)
Bidirectional 2;
System responses are not be
processed
Maximum number of receivers (transmitter
and receiver)
2 32
Distance between first and last device 15 m 1,200 m
Terminating resistors no yes
Max. transmission rate 115,200 Bit/s 10 MBit/s
Transmitter permitted driver output voltage ± 25 V 7…12 V
Driver output signal without load ± 15 V ± 6 V
Driver output signal with load ± 15 V ± 2 V
Driver load 3…7 KOhm 54 Ohm
Receiver input voltage ± 15 V 7…12 V
Sensitivity ± 3 V ± 200 mV
Input resistance 3…7 KOhm 12 KOhm
Note: As technical properties of serial interface components vary, transmission rate and line length data
provided here constitute maximum limits.