5.5.3 Alarm reset and silencing
Most alarms can be configured to auto-reset when the condition that causes the
alarm stops.
The alarms are manually reset through the HMI, the digital input, or Modbus.
The alarms can also be silenced. When an alarm is silenced only, the HMI alarm
LED still flashes and the alarm is still shows on the screen in the Alarms menu.
5.6 Running data and history data
Running data and history are stored in the controller. The data is also accessible
through remote communication.
Present alarm data
Ceased alarm data
Pump information
Well information