Step Display/Result
5.
Press
to select LOCAL. The LO/RE light will turn on.
STOP
6.
Press to run the motor at 5 Hz. The RUN light will turn on.
STOP
Off On
7.
With SW1 closed, the drive runs the motor at Multi-Step Speed 2
(20 Hz).
8.
With SW1 open and SW2 closed, the drive runs the motor at
Multi-Step 3 (50 Hz).
9.
With both SW1 and SW2 closed, the drive runs the motor at
Multi-Step 4 (60 Hz).
10.
Press
STOP
to stop the drive. The RUN light will flash until the
motor comes to a complete stop.
STOP
Flashing Off
<1> When the frequency reference is assigned to the LED operator (b1-01=0), the first step in a multi-step speed
sequence comes from d1-01.
Note: When a
run command is input from the control circuit terminal, the frequency reference value is selected
as follows:
When b1-01 = 0 and the run command is given, the drive uses the frequency set to d1-01.
When b1-01 = 1 and the run command is given, the drive uses the frequency reference value input to
analog control terminal A1.