Table 4.5 Drives with Heavy Duty Default Carrier Frequency of 10 kHz
200 V Single Phase Units 200 V Three Phase Units
Model Jo
Rated Current [A]
Model Jo
Rated Current [A]
2 kHz 10 kHz 15 kHz 2 kHz 10 kHz 15 kHz
BA0001 1.2 0.8 0.6 2A0001 1.2 0.8 0.6
BA0002 1.9 1.6 1.3 2A0002 1.9 1.6 1.3
BA0003 3.5 3.0 2.4 2A0004 3.5 3.0 2.4
BA0006 6.0 5.0 4.0 2A0006 6.0 5.0 4.0
Table 4.6 Drives with Heavy Duty Default Carrier Frequency of 8 kHz
200 V Single Phase Units 200 V Three Phase Units 400 V Three Phase Units
Model
Jo
Rated Current [A]
Model
Jo
Rated Current [A]
Model
Jo
Rated Current [A]
2 kHz 8 kHz 15 kHz 2 kHz 8 kHz 15 kHz 2 kHz 8 kHz 15 kHz
BA0010
9.6 8.0 6.4 — — — — 4A0001 1.2 1.2 0.7
—
— — — 2A0010 9.6 8.0 6.4 4A0002 2.1 1.8 1.1
—
— — — 2A0012 12.0 11.0 8.8 4A0004 4.1 3.4 2.0
— — — — — — — — 4A0005 5.4 4.8 2.9
— — — — 2A0020 19.6 17.5 14.0 4A0007 6.9 5.5 3.3
— — — — — — — — 4A0009 8.8 7.2 4.3
— — — —
— — — —
4A0011 11.1 9.2 5.5
u
Multi-Step Speed Operation (4-Step Speed)
Select up
to 9 preset references (including Jog reference) using two multi-function inputs S4
and S5. Two multi-step references can be selected using two multi-function inputs as
illustrated in Figure 4.14.
n
Multi-Step Speed Operation Parameters
No. Name Description
d1-01 Frequency Reference 1 Frequency reference. o1-03 determines the units, with Hz as the default.
d1-02 Frequency Reference 2
Frequency reference when multi-function input “Multi-Step Speed Reference 1"
(H1-oo = 3) is on. Setting unit: set by o1-03.
d1-03 Frequency Reference 3
Frequency reference when multi-function input “Multi-Step Speed Reference 2”
(H1-oo = 4) is on. Setting unit: set by o1-03.
d1-04 Frequency Reference 4
Frequency reference when multi-function input “Multi-Step Speed Reference 1,
2" (H1-oo = 3 and 4) are both on. Setting unit: set by o1-03.
4.5 Basic Operation
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
97
4
Start-Up Programming
& Operation