u
E: Motor Parameters
E parameters set V/f characteristics and motor-related data.
No. Name Description Range Def. Mode
Addr.
Hex
Pg.
E1: V/f Pattern Characteristics
Use E1 parameters to set V/f characteristics for the motor.
E1-01
<1>
Input Voltage
Setting
This parameter must be set to the power supply
voltage.
WARNING!
Drive
input voltage (not motor voltage)
must be set in E1-01 for the protective features of the
drive to function properly. Failure to do so may result
in equipment damage and/or death or personal
injury.
155 to
255
230 S 300 101
E1-03
V/f Pattern
Selection
F: Custom V/f. E1-04 through E1-10 settings define
the V/f pattern.
F F O 302
E1-04
Maximum
Output
Frequency
To set linear V/f characteristics, set the same values
for E1-07 and E1-09. In this case, the setting for
E1-08 will be disregarded. Ensure that the four
frequencies are set according to these rules:
E1-04 ≥ E1-06> E1-07 ≥ E1-09
E1-05
E1-08
E1-10
E1-09 E1-07 E1-06 E1-04
VACrms Out (V)
Frequency (Hz)
40.0 to
400.0
60
Hz
S 303 101
E1-05
<1>
Maximum
Output
Voltage
0.0 to
255.0
230
V
S 304 101
E1-06
Base
Frequency
0.0 to
E1-04
60
Hz
O 305 101
E1-07
Middle
Output
Frequency
0.0 to
E1-04
3.0
Hz
O 306 101
E1-08
<1>
Middle
Output
Frequency
Voltage
0.0 to
255.0
18.4
V
O 307 101
E1-09
Minimum
Output
Frequency
0.0 to
E1-04
1.5
Hz
S 308 101
E1-10
<1>
Minimum
Output
Frequency
Voltage
0.0 to
255.0
13.8
V
O 309 101
E2: Motor Parameters
Use E2 parameters to set motor-related data.
E2-01
Motor Rated
Current
Sets the motor nameplate full load current in
amperes.
Note: Set E2-03 (Motor No-Load Current) before
making changes to E2-01. Setting E2-01 < E2-03 will
trigger an oPE02 error.
10 to
200% of
drive
rated
current
<2> S 30E 104
E2-02
Motor Rated
Slip
Sets the motor rated slip in Hertz.
0.00 to
20.00
<2> O 30F 104
B.2 Parameter Table