Item Specification
Environment
Storage/Installation
Area
Indoors
Ambient
Temperature
-10 to +40 °C (IP20/NEMA Type 1)
<5>
-10 to +50 °C (IP20/Open-Chassis)
Humidity 95% RH or less with no condensation
Storage Temperature -20 to +60 °C allowed for short-term transport of the product
Altitude
Up to 1000 meters without derating; up to 3000 meters with output
current and voltage derating.
Shock, Impact
10 to 20 Hz: 9.8 m/s
2
20 to 55 Hz: 5.9 m/s
2
Surrounding Area
Install the drive in an area free from:
oil mist and dust
metal shavings, oil, water or other foreign materials
radioactive materials
combustible materials
harmful gases and liquids
excessive vibration
chlorides
direct sunlight
Orientation Install the drive vertically to maintain maximum cooling effects
Standards
UL508C
EN61800-3, EN61800-5-1
Protective Enclosure
IP20/Open-Chassis
IP20/NEMA Type 1
<5>
Cooling Method
CIMR-JoBA0001 to 0006: self-cooled
CIMR-JoBA0010: cooling fan
CIMR-Jo2A0001 to 0004: self-cooled
CIMR-Jo2A0006 to 0020: cooling fan
CIMR-Jo4A0001 to 0004: self-cooled
CIMR-Jo4A0005 to 0011: cooling fan
<1> Instantaneous average
deceleration torque refers to the torque required to decelerate the motor (uncoupled from
the load) from the rated motor speed down to zero in the shortest time.
<2> Ensure that Stall Prevention Selection during Deceleration is disabled (L3-04 = 0) or set to 3 when using a
braking resistor or the Braking Resistor Unit. The default setting for the stall prevention function will interfere
with the braking resistor.
<3> Overload protection may be triggered when operating with 150% of the rated output current if the output
frequency is less than 6 Hz.
<4> Ground protection cannot be provided under the following circumstances when a ground fault is likely in the
motor windings during run: Low ground resistance for the motor cable and terminal block; low ground resistance
for the motor cable and terminal block; or the drive is powered up from a ground short.
<5> All models have an IP20/Open-Chassis enclosure as standard. Use the NEMA Type 1 Kit option to convert
drives to an IP20/NEMA Type 1 enclosure rating.
A.4 Drive Specifications
204
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide