Model
Number
CIMR-Jo
Heavy Duty (Carrier Frequency 8 kHz) Normal Duty (Swing PWM equal 2 kHz)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
Rated
Amps (A)
Heatsink
Loss (W)
Interior
Unit Loss
(W)
Total
Loss (W)
4A0007 5.5 81.0 30.7 111.7 6.9 58.5 28.4 86.9
4A0009 7.2 84.6 32.9 117.5 8.8 63.7 31.4 95.1
4A0011 9.2 107.2 41.5 148.7 11.1 81.7 46.0 127.7
A.5 Drive Watt Loss Data
206