No. Name Description Range Def. Mode
Addr.
Hex
Pg.
o2-04
Drive Model
Selection
Sets the drive model.
This
parameter
only needs to be set when installing a
new control board. Do not change for other reason.
0 to FF
dep.
on
drive
spec.
O 508
o2-05
Frequency
Reference
Setting
Method
Selection
Selects if the ENTER key must be pressed when
inputting the frequency reference by the operator
keypad.
0: Data/Enter key must be pressed to enter a frequency
reference.
1: Data/Enter key is not required. The frequency
reference is adjusted by the UP and DOWN keys.
Note: When o2-05 is set to 1, the power supply to the
drive must remain on for at least 5 seconds after
making changes to the frequency reference.
0, 1 0 O 509
o2-06
Operation
Selection
when Digital
Operator is
Disconnected
Sets drive action when the digital operator is removed
in LOCAL mode or with b1-02 = 0 (valid for optional
remote operator only).
0: The drive will continue operation
1: The drive will trigger a fault (oPr) and the motor
will coast to stop
0, 1 0 O 50A
o2-09 Factory use.
o3: Copy Function
Use o3 parameters to Read, Copy and Verify the parameter settings to and from the drive.
o3-01
Copy
Function
Selection
Selects the copy function operation.
0: No action
1: READ - All parameters are read from the drive and
stored in the LED operator.
2: COPY - All parameters are copied from the LED
operator to the drive.
3: VERIFY - Parameter settings in the drive are
compared to those in the LED operator.
Note: When using the copy function, the drive model
number (o2-04) and the software number (U1-26)
must match or an error will occur.
0 to 3 0 O 515
o3-02
Copy
Allowed
Selection
Locks the READ operation to prevent accidental
overwriting of the data stored in the LED operator.
0: READ operation prohibited
1: READ operation allowed
0, 1 0 O 516
o4: Maintenance Period
Use o4 parameters to perform maintenance.
o4-01
Accumulated
Operation
Time Setting
Sets the value for the cumulative operation time of the
drive in units of 10 h.
0 to
9999
0 O 50B
o4-02
Accumulated
Operation
Time
Selection
Determines, how the cumulative operation time
(U4-01) is counted.
0: Logs power-on time
1: Logs operation time when the drive output is active
(output operation time).
0, 1 0 O 50C
B.2 Parameter Table
230
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide