Table C.7 Factory Recommended Drive Branch Circuit Protection
Drive Model
CIMR-Jo
Non-Time Delay
Class T Fuse Type
(Manufacturer: Ferraz)
Rated Voltage:
600 Vac, 200 kAIR
Fuse Ampere
Rating (A)
Fuse Type
(Manufacturer:
Bussmann)
Rated Voltage:
500 Vac, 200 kAIR
Fuse Ampere
Rating (A)
200 V Class Single-Phase Drives
BA0001 A6T6 6 FWH-25A14F 25
BA0002 A6T10 10 FWH-25A14F 25
BA0003 A6T20 20 FWH-60B 60
BA0006 A6T40 40 FWH-80B 80
BA0010 A6T40 40 FWH-100B 100
200 V Class Three-Phase Drives
2A0001 A6T3 3 FWH-25A14F 25
2A0002 A6T6 6 FWH-25A14F 25
2A0004 A6T15 15 FWH-25A14F 25
2A0006 A6T20 20 FWH-25A14F 25
2A0010 A6T25 25 FWH-70B 70
2A0012 A6T25 25 FWH-70B 70
2A0020 A6T40 40 FWH-90B 90
400 V Class Three-Phase Drives
4A0001 A6T3 3 FWH-40B 40
4A0002 A6T6 6 FWH-40B 40
4A0004 A6T15 15 FWH-50B 50
4A0005 A6T20 20 FWH-70B 70
4A0007 A6T25 25 FWH-70B 70
4A0009 A6T25 25 FWH-90B 90
4A0011 A6T30 30 FWH-90B 90
C.3 UL Standards
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
251
C
Standards Compliance