1.17 U: Monitors
110 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
No.
(Hex.)
Name Description MFAO Signal Level
U1-10
(0049)
Input Terminal Status
Shows the status of the MFDO terminal where = ON and = OFF.
For example, U1-10 shows when terminals S1 and S3 are ON.
bit0 : Terminal S1 (MFDI 1)
bit1 : Terminal S2 (MFDI 2)
bit2 : Terminal S3 (MFDI 3)
bit3 : Terminal S4 (MFDI 4)
bit4 : Terminal S5 (MFDI 5)
bit5 : Terminal S6 (MFDI 6)
bit6 : Terminal S7 (MFDI 7)
bit7 : Not used (normal value of [ ]).
No signal output available
U1-11
(004A)
Output Terminal Status
Shows the status of the MFDO terminal where = ON and = OFF.
For example, U1-11 shows when terminals MA and P2 are ON.
Note:
When H2-xx = 100 to 1A7 [U1-11 Inverse U1-11 Output of Function], U1-11 does not show the
status in inverse.
bit0 : Terminal MA/MB-MC
bit1 : Terminal P1-C1
bit2 : Terminal P2-C2
bit3 : Not used (normal value of [ ]).
bit4 : Not used (normal value of [ ]).
bit5 : Not used (normal value of [ ]).
bit6 : Not used (normal value of [ ]).
bit7 : Not used (normal value of [ ]).
No signal output available
U1-12
(004B)
Drive Status
Shows drive status where = ON and = OFF.
For example, U1-12 shows during run with the Reverse Run command.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive Ready
bit6 : During minor fault detection
bit7 : During fault detection
No signal output available
U1-13
(004E)
Terminal A1 Level
Shows the signal level of terminal A1.
Unit: 0.1%
10 V = 100% (0 V to +10 V)
U1-14
(004F)
Terminal A2 Level
Shows the signal level of terminal A2.
Unit: 0.1%
10 V = 100% (0 V to +10 V)
U1-16
(0053)
SFS Output Frequency
Shows the output frequency after soft start. Shows the frequency with acceleration and deceleration
times and S-curves. Parameter o1-03 [Keypad Display Unit Selection] sets the display units.
Unit: 0.01 Hz
10 V = Maximum frequency
(0 V to +10 V)
U1-18
(0061)
oPE Fault Parameter
Shows the parameter number that caused the oPE02 [Parameter Range Setting Error] or oPE08
[Parameter Selection Error].
No signal output available
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Related product manuals