1.19 Parameters that Change from the Default Settings with E3-01 [Motor 2 Control Mode Selection]
128 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
1.19 Parameters that Change from the Default Settings with
E3-01 [Motor 2 Control Mode Selection]
The values for the parameters in these tables depend on the values for parameter E3-01. When you change the setting
for E3-01, the default settings will change.
No. Name Range Unit
Motor 2 Control Method (setting value of E3-01)
V/f
(0)
OLV
(2)
C3-21 Motor 2 Slip Compensation Gain 0.0 - 2.50 0.1 0.0 1.0
C3-22 Motor 2 Slip Comp Delay Time 0 - 10000 1 ms 2000 200
E3-04
Motor 2 Maximum Output
Frequency
40.0 - 590.0 0.1 Hz 60.0 60.0
E3-05 Motor 2 Maximum Output Voltage
0.0 - 255.0
*1
0.1 V 200.0 200.0
E3-06 Motor 2 Base Frequency 0.0 - 590.0 0.1 Hz 60.0 60.0
E3-07 Motor 2 Mid Point A Frequency 0.0 - 590.0 0.1 Hz 3.0 3.0
E3-08 Motor 2 Mid Point A Voltage
0.0 - 255.0
*1
0.1 V 15.0 11.0
E3-09
Motor 2 Minimum Output
Frequency
0.0 - 590.0 0.1 Hz 1.5 0.5
E3-10 Motor 2 Minimum Output Voltage
0.0 - 255.0
*1
0.1 V 9.0 2.0
E3-11 Motor 2 Mid Point B Frequency 0.0 - 590.0 Determined by o1-04 0.0 0.0
E3-12 Motor 2 Mid Point B Voltage
0.0 - 255.0
*1
0.1 V 0.0 0.0
E3-13 Motor 2 Base Voltage
0.0 - 255.0
*1
0.1 V 0.0 0.0
*1 This is the value for 200 V class drives. Double the value for 400 V class drives.