Parameter List
1
1.7 d: Reference Settings
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 37
1.7 d: Reference Settings
d1: Frequency Reference
No.
(Hex.)
Name Description
Default
(Range)
d1-01
(0280)
RUN
Reference 1
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-02
(0281)
RUN
Reference 2
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-03
(0282)
RUN
Reference 3
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-04
(0283)
RUN
Reference 4
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-05
(0284)
RUN
Reference 5
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-06
(0285)
RUN
Reference 6
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-07
(0286)
RUN
Reference 7
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-08
(0287)
RUN
Reference 8
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-09
(0288)
RUN
Reference 9
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-10
(028B)
RUN
Reference 10
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
d1-11
(028C)
RUN
Reference 11
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6 [Control Method Selection = AOLV/PM], the default setting is o1-03 = 1
[0.01% (100% = E1-04)].
0.00 Hz
(0.00 - 590.00 Hz)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV