EasyManua.ls Logo

YASKAWA GA500 GA50U Series

YASKAWA GA500 GA50U Series
524 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.6 C: Tuning
36 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
No.
(Hex.)
Name Description
Default
(Range)
C6-03
(0225)
Carrier Frequency Upper
Limit
Sets the upper limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
C6-04
(0226)
Carrier Frequency Lower
Limit
Sets the lower limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
C6-05
(0227)
Carrier Freq Proportional
Gain
Sets the proportional gain for the carrier frequency. Set C6-02 = F [Carrier Frequency Selection =
User Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(0 - 99)
C6-09
(022B)
Carrier Freq at Rotational
Tune
Sets the Auto-Tuning carrier frequency. Usually it is not necessary to change this setting.
0 : 5 kHz
1 : Use C6-03
0
(0, 1)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV