EasyManua.ls Logo

YASKAWA GA500 GA50U Series

YASKAWA GA500 GA50U Series
524 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
2
2.3 b: Application
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 185
Purpose Procedure Results
Prevent overshoot. Set b5-05 [Derivative Time (D)] to a smaller value.
Set b5-03 [Integral Time (I)] to a larger value.
Quickly stabilize control. Set b5-05 [Derivative Time (D)] to a larger value.
Set b5-03 [Integral Time (I)] to a smaller value.
Prevent long-cycle oscillations. Set b5-03 [Integral Time (I)] to a larger value.
Prevent short-cycle oscillations. Set b5-05 [Derivative Time (D)] to a smaller value.
If you set b5-05 = 0.00 [Derivative Time (D) =
disabling D control] and it does not stop
oscillation, then set b5-02 [Proportional Gain (P)]
to a smaller value or set b5-08 [PID Primary
Delay Time Constant] to a larger value.
EZ Sleep/Wake-up Functionality
Set b5-89 = 1 [Sleep Method Selection = EZ Sleep/Wake-up] to enable the EZ Sleep/Wake-up function.
Note:
When b5-89 = 0 [Sleep Mode Selection = Standard], the EZ Sleep function and related parameters are disabled. Parameter b5-91 [EZ Sleep
Minimum Speed] is not included in this rule.
Set b5-89 = 1 to disable b5-15 [PID Sleep Function Start Level].

Table of Contents

Related product manuals