2.5 d: References
230 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
d1-11: Reference 11
No.
(Hex.)
Name Description
Default
(Range)
d1-11
(028C)
RUN
Reference 11
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 11.
d1-12: Reference 12
No.
(Hex.)
Name Description
Default
(Range)
d1-12
(028D)
RUN
Reference 12
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 12.
d1-13: Reference 13
No.
(Hex.)
Name Description
Default
(Range)
d1-13
(028E)
RUN
Reference 13
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 13.
d1-14: Reference 14
No.
(Hex.)
Name Description
Default
(Range)
d1-14
(028F)
RUN
Reference 14
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
This parameter sets the frequency reference of Multi-Step Speed 14.
d1-15: Reference 15
No.
(Hex.)
Name Description
Default
(Range)
d1-15
(0290)
RUN
Reference 15
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV