2.6 E: Motor Parameters
250 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
The value set for E2-01 becomes the reference value for motor protection and the torque limit. Enter the motor rated
current written on the motor nameplate. Auto-Tuning the drive will automatically set E2-01 to the value input for T1-
04 [Motor Rated Current].
E2-02: Motor Rated Slip
No.
(Hex.)
Name Description
Default
(Range)
E2-02
(030F)
Motor Rated Slip
Sets motor rated slip.
Determined by o2-04, C6-01
(0.000 - 20.000 Hz)
This parameter value becomes the base slip compensation value. The drive automatically sets this parameter during
Auto-Tuning. When you cannot do Auto-Tuning, calculate the motor rated slip with the information on the motor
nameplate and this formula:
E2-02 = f - (n × p) / 120
f: Motor rated frequency (Hz)
n: Rated motor speed (min
-1
(r/min))
p: Number of motor poles
E2-03: Motor No-Load Current
No.
(Hex.)
Name Description
Default
(Range)
E2-03
(0310)
Motor No-Load Current
Sets the no-load current for the motor in amps when operating at the rated frequency and the no-load
voltage.
Determined by o2-04, C6-01
(0 to E2-01)
Note:
When the drive model changes, the display units for this parameter also change.
0.01 A: B001 - B018, 2001 - 2042, 4001 - 4023
0.1 A: 2056 - 2082, 4031 - 4060
The drive automatically sets this parameter during Auto-Tuning. When you cannot do Auto-Tuning, you can also use
the motor no-load current on the motor test report to enter this value manually. Get the test report from the motor
manufacturer.
Note:
The default setting of the no-load current is for a 4-pole motor recommended by Yaskawa.
E2-04: Motor Pole Count
No.
(Hex.)
Name Description
Default
(Range)
E2-04
(0311)
Motor Pole Count
Sets the number of motor poles.
4
(2 - 120)
Note:
When A1-02 = 0 [Control Method Selection = V/f], the maximum value is 120.
When A1-02 = 2 [OLV], the maximum value is 48.
Auto-Tuning automatically sets this parameter to the value of [Number of Motor Poles].
E2-05: Motor Line-to-Line Resistance
No.
(Hex.)
Name Description
Default
(Range)
E2-05
(0312)
Motor Line-to-Line
Resistance
Sets the line-to-line resistance for the motor stator windings.
Determined by o2-04, C6-01
(0.000 - 65.000 Ω)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the resistance per phase.
Auto-Tuning automatically sets this parameter. If you cannot do Auto-Tuning, use the test report from the motor
manufacturer to configure the settings. Use one of these formulas to calculate the motor line-to-line resistance:
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV