Parameter Details
2
2.7 F: Options
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 273
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps
F6-14: BUS Error Auto Reset
No.
(Hex.)
Name Description
Default
(Range)
F6-14
(03BB)
BUS Error Auto Reset
Sets the automatic reset function for bUS [Option Communication Errors].
0
(0, 1)
0 : Disable
1 : Enabled
F6-15: Comm. Option Parameters Reload
No.
(Hex.)
Name Description
Default
(Range)
F6-15
(0B5B)
Comm. Option Parameters
Reload
Sets the update method when you change F6-xx, F7-xx [Communication Options].
0
(0 - 2)
Note:
Set F6-15 = 0, 1 to reload F6-xx, F7-xx.
Set F6-15 = 0, 1 to reset the display on the keypad to 0.
0 : Reload at Next Power Cycle
Restart the drive to update parameters.
1 : Reload Now
The changed parameters are updated without restarting the drive.
2 : Cancel Reload Request
Cancels CyPo [Cycle Power to Accept Changes].
F6-16: Gateway Mode
No.
(Hex.)
Name Description
Default
(Range)
F6-16
(0B8A)
Gateway Mode
Sets the gateway mode operation and the number of connected slave drives.
0
(0 to 4)
0 : Disabled
1 : Enabled: 1 Slave Drives
2 : Enabled: 2 Slave Drives
3 : Enabled: 3 Slave Drives
4 : Enabled: 4 Slave Drives
F6-20: MECHATROLINK Station Address
No.
(Hex.)
Name Description
Default
(Range)
F6-20
(036B)
MECHATROLINK Station
Address
Sets the station address for MECHATROLINK communication. Change the parameter then cycle
power on the drive.
0021h
(MECHATROLINK-II:
0020h - 003Fh,
MECHATROLINK-III:
0003h - 00EFh)