Parameter Details
2
2.7 F: Options
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 281
F7-11: Gateway Address 3
No.
(Hex.)
Name Description
Default
(Range)
F7-11
(03EF)
Gateway Address 3
Sets the third octet of the gateway address of the connected network.
1
(0 - 255)
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
F7-12: Gateway Address 4
No.
(Hex.)
Name Description
Default
(Range)
F7-12
(03F0)
Gateway Address 4
Sets the fourth octet of the gateway address of the connected network.
1
(0 - 255)
Note:
Set this parameter when F7-13 = 0 [Address Mode at Startup = Static].
F7-13: Address Mode at Startup
No.
(Hex.)
Name Description
Default
(Range)
F7-13
(03F1)
Address Mode at Startup
Sets the method to set option card IP addresses.
2
(0 - 2)
0 : Static
1 : BOOTP
2 : DHCP
Note:
The following setting values are available when using the PROFINET communication option card (SI-EP3).
0: Static
2: DCP
When F7-13 = 0, set parameters F7-01 to F7-12 [IP Address 1 to Gateway Address 4] to set the IP Address. Be sure to set a different IP
address for each drive on the network.
F7-14: Duplex Mode Selection
No.
(Hex.)
Name Description
Default
(Range)
F7-14
(03F2)
Duplex Mode Selection
Sets the duplex mode setting method.
1
(0 - 8)
0 : Half/Half
1 : Auto/Auto
2 : Full/Full
3 : Half/Auto
Port 1 is set to Half and port 2 is set to Auto.
4 : Half/Full
Port 1 is set to Half and port 2 is set to Full.
5 : Auto/Half
Port 1 is set to Auto and port 2 is set to Half.
6 : Auto/Full
Port 1 is set to Auto and port 2 is set to Full.
7 : Full/Half
Port 1 is set to Full and port 2 is set to Half.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV