Parameter Details
2
2.7 F: Options
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 283
F7-22: EtherNet/IP Time Scaling
No.
(Hex.)
Name Description
Default
(Range)
F7-22
(03FA)
EtherNet/IP Time Scaling
Sets the scaling factor for the time monitor in the EtherNet/IP Class ID 2AH Object.
0
(-15 - +15)
F7-23 to F7-32: Dynamic Out Param 1 to 10 for CommCard
No.
(Hex.)
Name Description
Default
(Range)
F7-23 to F7-27
(03FB - 03FF)
F7-28 to F7-32
(0370 - 0374)
Dynamic Out Param 1 to 10
for CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0. When you use a ProfiNet option, set F7-23 to F7-27 to configurable Output 1-
5.
0
F7-33 to F7-42: Dynamic In Param 1 to 10 for CommCard
No.
(Hex.)
Name Description
Default
(Range)
F7-33 to F7-42
(0375 - 037E)
Dynamic In Param 1 to 10
for CommCard
When you use an Ethernet/IP option, sets Input Assembly 166. The drive sends the values from the
MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive
returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and
the value sent to Input Assembly 166 is not defined. When you use a ProfiNet option, set F7-33 to
F7-37 to configurable inputs 1-5.
0
F7-60: PZD1 Write (Control Word)
No.
(Hex.)
Name Description
Default
(Range)
F7-60
(0780)
PZD1 Write (Control Word)
When you use a Profibus option, set the MEMOBUS/Modbus address for PZD1 (PPO output). PZD1
(PPO output) functions as the STW when F7-60 = 0 to 2.
0
F7-61: PZD2 Write (Frequency Reference)
No.
(Hex.)
Name Description
Default
(Range)
F7-61
(0781)
PZD2 Write (Frequency
Reference)
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD2 (PPO output).
PZD2 (PPO output) functions as the HSW when F7-61 = 0 to 2.
0
F7-62: PZD3 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-62
(0782)
PZD3 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD3 (PPO output). A
value of 0, 1, or 2 will disable the PZD3 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-63: PZD4 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-63
(0783)
PZD4 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD4 (PPO output). A
value of 0, 1, or 2 will disable the PZD4 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV