Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 289
Note:
The default setting is 0 when the drive is initialized for 3-Wire Initialization [A1-03 = 3330].
H1-06: Terminal S6 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-06
(0403)
Terminal S6 Function
Selection
Sets the function for MFDI terminal S6.
4
(0 - 1FF)
Note:
The default setting is 3 when the drive is initialized for 3-Wire Initialization [A1-03 = 3330].
H1-07: Terminal S7 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-07
(0404)
Terminal S7 Function
Selection
Sets the function for MFDI terminal S7.
6
(0 - 1FF)
Note:
The default setting is 4 when the drive is initialized for 3-Wire Initialization [A1-03 = 3330].
H1-21: Terminal S1 Function Select 2
No.
(Hex.)
Name Description
Default
(Range)
H1-21
(0B70)
Terminal S1 Function
Selection 2
Sets the second function for MFDI terminal S1.
F
(1 - 19F)
When MFDI terminal S1 activates, it will operate the function set to H1-01 [Terminal S1 Function Selection] and the
function set to H1-21 at the same time.
When the setting value is F, the function is disabled.
H1-22: Terminal S2 Function Select 2
No.
(Hex.)
Name Description
Default
(Range)
H1-22
(0B71)
Terminal S2 Function Select
2
Sets the second function for MFDI terminal S2.
F
(1 - 19F)
When MFDI terminal S2 activates, it will operate the function set to H1-02 [Terminal S2 Function Selection] and the
function set to H1-22 at the same time.
When the setting value is F, the function is disabled.
H1-23: Terminal S3 Function Select 2
No.
(Hex.)
Name Description
Default
(Range)
H1-23
(0B72)
Terminal S3 Function
Selection 2
Sets the second function for MFDI terminal S3.
F
(1 - 19F)
When MFDI terminal S3 activates, it will operate the function set to H1-03 [Terminal S3 Function Selection] and the
function set to H1-23 at the same time.
When the setting value is F, the function is disabled.
H1-24: Terminal S4 Function Selection 2
No.
(Hex.)
Name Description
Default
(Range)
H1-24
(0B73)
Terminal S4 Function
Selection 2
Sets the second function for MFDI terminal S4.
F
(1 - 19F)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents