Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 339
■ 6: DC Injection Braking Current
Setting Value Function Description
6 DC Injection Braking
Current
Enters a signal to adjust the current level used for DC Injection Braking when the drive rated output current is 100%.
Note:
When you set this function, it will disable the setting value of b2-02 [DC Injection Braking Current].
Figure 2.85 DC Injection Braking Current through Analog Input
■ 7: Torque Detection Level
Setting Value Function Description
7 Torque Detection Level
Enters a signal to adjust the overtorque/undertorque detection level.
When A1-02 = 0, 5 [Control Method Selection = V/f, OLV/PM], the drive rated current is 100%. When A1-02 = 2, 6,
8 [OLV, AOLV/PM, or EZOLV], the motor rated current is 100%.
Note:
Use this function with L6-01 [Torque Detection Selection 1]. This parameter functions as an alternative to L6-02 [Torque Detection Level 1].
■ 8: Stall Prevent Level during Run
Setting Value Function Description
8 Stall Prevent Level during
Run
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
Note:
The drive will use the smaller value of these values for Stall Prevent Level during Run:
• Multi-function analog input terminal analog input value
• L3-06 [Stall Prevent Level during Run]
Figure 2.86 Stall Prevention Level during Run with Analog Input
■ 9: Output Frequency Lower Limit
Setting Value Function Description
9 Output Frequency Lower
Limit
Enters a signal to adjust the output frequency lower limit level as a percentage of the maximum output frequency.