Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 347
■ H5-06: Drive Transmit Wait Time
No.
(Hex.)
Name Description
Default
(Range)
H5-06
(042A)
Drive Transmit Wait Time
Sets the time to wait to send a response message after the drive receives a command message from
the master.
5 ms
(0 - 65 ms)
Figure 2.91 Drive Transmit Wait Time
■ H5-09: CE Detection Time
No.
(Hex.)
Name Description
Default
(Range)
H5-09
(0435)
CE Detection Time
Sets the detection time for CE [Modbus Communication Error] issues when communication stops.
2.0 s
(0.0 - 25.0 s)
■ H5-10: Modbus Register 0025H Unit Sel
No.
(Hex.)
Name Description
Default
(Range)
H5-10
(0436)
Modbus Register 0025H
Unit Sel
Sets the unit of measure used for the MEMOBUS/Modbus communications monitor register 0025H
(output voltage reference monitor).
0
(0, 1)
0 : 0.1 V units
1 : 1 V units
■ H5-11: Comm ENTER Command Mode
No.
(Hex.)
Name Description
Default
(Range)
H5-11
(043C)
RUN
Comm ENTER Command
Mode
Sets the function to make the Enter command necessary to change parameters through MEMOBUS/
Modbus communications.
1
(0, 1)
0 : ENTER Command Required
Make all parameter changes then input the Enter command. You must use the Enter command to enable changes to
parameters.
1 : ENTER Command Not Required
It is not necessary to input the Enter command to change parameters.
■ H5-12: Run Command Method Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-12
(043D)
Run Command Method
Selection
Sets the input method for the Run command when b1-02 = 2 [Run Command Selection 1 =
Memobus/Modbus Communications] or b1-16 = 2 [Run Command Selection 2 = Memobus/Modbus
Communications].
0
(0, 1)
0 : FWD/Stop, REV/Stop
The drive uses bit 0 in command data 0001H of the MEMOBUS register in the motor forward Run command (bit 0 =
1) and the stop command (bit 0 = 0). The drive uses bit 1 in the motor reverse Run command (bit 1 = 1) and the stop
command (bit 1 = 0).