2.8 H: Terminal Function Selection
354 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
■ H7-03: Virtual Multi-Function Input 3
No.
(Hex.)
Name Description
Default
(Range)
H7-03
(1187)
Expert
Virtual Multi-Function Input
3
Sets the function that enters the virtual input set in H7-14 [Virtual Multi-Function Output 3].
F
(1 - 19F)
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
■ H7-04: Virtual Multi-Function Input 4
No.
(Hex.)
Name Description
Default
(Range)
H7-04
(1188)
Expert
Virtual Multi-Function Input
4
Sets the function that enters the virtual input set in H7-16 [Virtual Multi-Function Output 4].
F
(1 - 19F)
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
■ H7-10: Virtual Multi-Function Output 1
No.
(Hex.)
Name Description
Default
(Range)
H7-10
(11A4)
Expert
Virtual Multi-Function
Output 1
Sets the function for virtual digital output 1.
F
(0 - 1A7)
■ H7-11: Virtual Output 1 Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H7-11
(11A5)
Expert
Virtual Output 1 Delay Time
Sets the minimum ON time for virtual digital output 1.
0.1 s
(0.0 - 25.0 s)
■ H7-12: Virtual Multi-Function Output 2
No.
(Hex.)
Name Description
Default
(Range)
H7-12
(11A6)
Expert
Virtual Multi-Function
Output 2
Sets the function for virtual digital output 2.
F
(0 - 1A7)
■ H7-13: Virtual Output 2 Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H7-13
(11A7)
Expert
Virtual Output 2 Delay Time
Sets the minimum ON time for virtual digital output 2.
0.1 s
(0.0 - 25.0 s)
■ H7-14: Virtual Multi-Function Output 3
No.
(Hex.)
Name Description
Default
(Range)
H7-14
(11A8)
Expert
Virtual Multi-Function
Output 3
Sets the function for virtual digital output 3.
F