Parameter Details
2
2.9 L: Protection Functions
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 363
L1-05: Motor Thermistor Filter Time
No.
(Hex.)
Name Description
Default
(Range)
L1-05
(0484)
Motor Thermistor Filter
Time
Sets the primary delay time constant for the PTC input signal entered to the drive. This parameter
prevents accidental motor overheat faults.
0.20 s
(0.00 - 10.00 s)
L1-08: oL1 Current Level
No.
(Hex.)
Name Description
Default
(Range)
L1-08
(1103)
oL1 Current Level
Sets the reference current for the motor 1 thermal overload detection. When the current level > 0.0 A,
you cannot set this value < 10% of drive rated current.
0.0 A
(0.0 A or 10% to 150% of
the drive rated current)
When L1-08 = 0.0 A, the drive uses E2-01 [Motor Rated Current (FLA)] to detect the motor overload protection. In
PM control mode, the drive uses E5-03 [PM Motor Rated Current (FLA)] to detect the motor overload protection.
When L1-08 0.0 A, the set value is the reference for motor overload protection.
Note:
Display is in these units:
0.01 A: B001 to B018, 2001 to 2042, 4001 to 4023
0.1 A: 2056 to 2082, 4031 to 4060
When the current level > 0.0 A, you cannot set this value < 10% of drive rated current.
L1-09: oL1 Current Level for Motor 2
No.
(Hex.)
Name Description
Default
(Range)
L1-09
(1104)
oL1 Current Level for Motor
2
Sets the reference current for the motor 2 thermal overload detection. When the current level > 0.0 A,
you cannot set this value < 10% of drive rated current.
0.0 A
(0.0 A or 10 to150% of the
drive rated current)
When L1-09 = 0.0 A, the drive uses E4-01 [Motor 2 Rated Current] to detect the motor overload protection.
When L1-09 0.0 A, the set value is the reference for motor overload protection.
Note:
Display is in these units:
0.01 A: B001 to B018, 2001 to 2042, 4001 to 4023
0.1 A: 2056 to 2082, 4031 to 4060
When the current level > 0.0 A, you cannot set this value < 10% of drive rated current.
L1-13: Motor Overload Memory Selection
No.
(Hex.)
Name Description
Default
(Range)
L1-13
(046D)
Motor Overload Memory
Selection
Sets the function that keeps the current electronic thermal protector value when the drive stops
receiving power.
1
(0, 1)
0 : Disabled
1 : Enabled
Sets if the drive will calculate the motor again when the drive is energized again.
L1-22: Leakage Current Filter Time1
No.
(Hex.)
Name Description
Default
(Range)
L1-22
(0768)
RUN
Leakage Current Filter
Time1
Sets the leakage current detection reduction filter time constant during constant speed run.
Determined by C6-02
(0.0 - 60.0 s)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV