Parameter Details
2
2.9 L: Protection Functions
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 383
■ L3-35: Speed Agree Width for Auto Decel
No.
(Hex.)
Name Description
Default
(Range)
L3-35
(0747)
Expert
Speed Agree Width for Auto
Decel
Sets the width for speed agreement when L3-04 = 2 [Stall Prevention during Decel = Intelligent
(Ignore Decel Ramp)]. Usually it is not necessary to change this setting.
0.00 Hz
(0.00 - 1.00 Hz)
Set this parameter when hunting occurs while you use a frequency reference through an analog input.
■ L3-36: Current Suppression Gain@Accel
No.
(Hex.)
Name Description
Default
(Range)
L3-36
(11D0)
Current Suppression
Gain@Accel
Sets the gain to suppress current and motor speed hunting during operation when L3-01 = 3 [Stall
Prevention during Accel = Current Limit Method]. Usually it is not necessary to change this setting.
Determined by A1-02
(0.0 - 100.0)
If there is vibration in the output current during acceleration, increase the setting value.
Note:
Set L3-01 = 3 [Stall Prevention during Accel = Current Limit Method] to enable this function.
■ L3-37: Current Limit P Gain @Accel
No.
(Hex.)
Name Description
Default
(Range)
L3-37
(11D1)
Expert
Current Limit P Gain
@Accel
Suppresses current hunting during acceleration. Usually it is not necessary to change this setting.
5 ms
(0 - 100 ms)
Note:
Set L3-01 = 3 [Stall Prevention during Accel = Current Limit Acceleration] to enable this function.
■ L3-38: Current Limit I Time @ Accel
No.
(Hex.)
Name Description
Default
(Range)
L3-38
(11D2)
Expert
Current Limit I Time @
Accel
Suppresses current hunting and overshooting that occurs when the drive stalls during acceleration.
Usually it is not necessary to change this setting.
10.0
(0.0 - 100.0)
Note:
Set L3-01 = 3 [Stall Prevention during Accel = Current Limit Method] to enable this function.
■ L3-39: Current Limit Filter Time@Accel
No.
(Hex.)
Name Description
Default
(Range)
L3-39
(11D3)
Current Limit Filter
Time@Accel
Sets the time constant to adjust the acceleration rate when L3-01 = 3 [Stall Prevention during Accel
= Current Limit Acceleration]. Usually it is not necessary to change this setting.
100.0 ms
(1.0 - 1000.0 ms)
Note:
Set L3-01 = 3 [Stall Prevention during Accel = Current Limit Acceleration] to enable this function.
■ L3-40: Current Limit S-Curve @ Acc/Dec
No.
(Hex.)
Name Description
Default
(Range)
L3-40
(11D4)
Current Limit S-Curve @
Acc/Dec
Sets the function to enable and disable the best S-curve characteristic used for current-limited
acceleration.
0
(0, 1)