Parameter Details
2
2.10 n: Special Adjustment
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 417
■ n8-24: ACR q Integral Time @PoleEst
No.
(Hex.)
Name Description
Default
(Range)
n8-24
(0557)
Expert
ACR q Integral Time
@PoleEst
Sets the integral time for current regulator q-axis control when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
0.0 ms
(0.0 - 100.0 ms)
■ n8-25: ACR q Limit @PoleEst
No.
(Hex.)
Name Description
Default
(Range)
n8-25
(0558)
Expert
ACR q Limit @PoleEst
Sets the q-axis limit of the current regulator when the drive estimates the initial pole. Usually it is not
necessary to change this setting.
0%
(0 - 150%)
■ n8-26: ACR d Gain @PoleEst
No.
(Hex.)
Name Description
Default
(Range)
n8-26
(0559)
Expert
ACR d Gain @PoleEst
Sets the proportional gain for current regulator d-axis control when the drive estimates the initial
pole. Usually it is not necessary to change this setting.
500
(0 - 2000)
■ n8-27: ACR d Integral Time @PoleEst
No.
(Hex.)
Name Description
Default
(Range)
n8-27
(055A)
Expert
ACR d Integral Time
@PoleEst
Sets the integral time for current regulator d-axis control when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
0.0 ms
(0.0 - 100.0 ms)
■ n8-28: ACR d Lim @PoleEst
No.
(Hex.)
Name Description
Default
(Range)
n8-28
(055B)
Expert
ACR d Lim @PoleEst
Sets the d-axis limit of the current regulator when the drive estimates the initial pole. Usually it is not
necessary to change this setting.
100%
(0 - 150%)
■ n8-35: Initial Pole Detection Method
No.
(Hex.)
Name Description
Default
(Range)
n8-35
(0562)
Initial Pole Detection
Method
Sets how the drive detects the position of the rotor when the motor starts.
Determined by A1-02
(0 - 2)
Note:
• When you use an SPM motor, set n8-35 = 0. When you use an IPM motor, set n8-35 = 0 to 2.
• When you set n8-35 = 1, do High Frequency Injection Auto-Tuning.
• When you set n8-35 = 0 or 2, always evaluate the drive with the equipment being used for the application. If the drive incorrectly detects
the polarity, the motor can rotate in the direction opposite of the Run command.
0 : Pull-in
Starts the rotor with pull-in current.
1 : High Frequency Injection
Injects high frequency to detect the rotor position. This setting can cause a loud excitation sound when the motor
starts.
Note:
When you set 1, do High Frequency Injection Auto-Tuning.
2 : Pulse Injection