2.11 o: Keypad-Related Settings
434 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
o1-50: Trend Plot 2 Scale Maximum Value
No.
(Hex.)
Name Description
Default
(Range)
o1-50
(11CA)
RUN
Trend Plot 2 Scale
Maximum Value
Sets the maximum value for the vertical axis used to display the monitor that was set in o1-25
[Custom Monitor 2] as a trend plot. This parameter is only available with an LCD keypad.
100.0%
(-299.9 - +300.0%)
Note:
Parameter o1-49 [Trend Plot 2 Scale Minimum Value] sets the lower limit. The lower limit is (o1-49 + 0.1)%.
o1-51: Trend Plot Time Scale Setting
No.
(Hex.)
Name Description
Default
(Range)
o1-51
(11CB)
RUN
Trend Plot Time Scale
Setting
Sets the time scale (horizontal axis) to display the trend plot. When you change this setting, the drive
automatically adjusts the data sampling time. This parameter is only available with an LCD keypad.
300 s
(1 - 3600 s)
o1-55: Analog Gauge Area Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-55
(11EE)
RUN
Analog Gauge Area
Selection
Sets the range used to display the monitor set in o1-24 [Custom Monitor 1] as an analog gauge. This
parameter is only available with an LCD keypad.
1
( 0, 1 )
0 : +/- Area ( - o1-56 ~ o1-56 )
1 : + Area ( 0 ~ o1-56 )
o1-56: Analog Gauge Area Setting
No.
(Hex.)
Name Description
Default
(Range)
o1-56
(11EF)
RUN
Analog Gauge Area Setting
Sets the value used to display the monitor set in o1-24 [Custom Monitor 1] as an analog meter. This
parameter is only available with an LCD keypad.
100.0%
(0.0 - 100.0%)
o1-58: Motor Power Unit Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-58
(3125)
Motor Power Unit Selection
Sets the setting unit for parameters that set the motor rated power.
1
(0, 1)
The drive shows these parameter values in the set units:
E2-11 [Motor Rated Power]
E4-11 [Motor 2 Rated Power]
E5-02 [PM Motor Rated Power]
E9-07 [Motor Rated Power]
T1-02 [Motor Rated Power]
T2-04 [PM Motor Rated Power]
T4-08 [Motor Rated Capacity]
0 : kW
Shows the motor output in kW units.
1 : HP
Shows the motor output in HP units.
Note:
When you use an LED keypad, use o1-58 to make sure that the units for the monitors and parameters are correct.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents