EasyManua.ls Logo

YASKAWA GA500 GA50U Series

YASKAWA GA500 GA50U Series
524 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.11 o: Keypad-Related Settings
446 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
No. Item
Number of
Characters
Description
15 Encoding data 4 Log Monitor Data 1 to 10 Code Data (Hex.)
Bits 0 through 9 show the encoding of log monitor data 1 1 through 10. A bit value of 1 shows that the data represents a
negative value. (Log monitor data 1 through 10 is absolute value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7 have values of 1, and the encoding data
= 0010010010 (Bin.) = 0092 (Hex.)
16 Row number 6 Row number (Hex.) in the data log file
o5-01: Log Start/Stop Selection
No.
(Hex.)
Name Description
Default
(Range)
o5-01
(1551)
RUN
Log Start/Stop Selection
Sets the data log function. This parameter is only available when using an LCD keypad.
0
(0 - 1)
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in o5-02 [Log Sampling Interval].
o5-02: Log Sampling Interval
No.
(Hex.)
Name Description
Default
(Range)
o5-02
(1552)
RUN
Log Sampling Interval
Sets the data log sampling cycle. This parameter is only available when using an LCD keypad.
100 ms
(100 - 60000 ms)
o5-03: Log Monitor Data 1
No.
(Hex.)
Name Description
Default
(Range)
o5-03
(1553)
RUN
Log Monitor Data 1
Sets the data log monitor. This parameter is only available with an LCD keypad.
101
(000, 101 - 999)
Note:
Set the number of the U monitor to record the data log.
For example, to show U1-01 [Frequency Reference], set o5-03 = 101. When it is not necessary to set data log monitors, set this parameter to
000. You cannot set U2 monitor [Fault Trace] or U3 Monitor [Fault History].
o5-04: Log Monitor Data 2
No.
(Hex.)
Name Description
Default
(Range)
o5-04
(1554)
RUN
Log Monitor Data 2
Sets the data log monitor. This parameter is only available when using an LCD keypad.
102
(000, 101 - 999)
Note:
Set the U monitor number you will log.
For example, to show U1-02 [Output Frequency], set o5-04 = 102. When it is not necessary to set data log monitor, set this parameter to
000.
o5-05: Log Monitor Data 3
No.
(Hex.)
Name Description
Default
(Range)
o5-05
(1555)
RUN
Log Monitor Data 3
Sets the data log monitor. This parameter is only available with an LCD keypad.
103
(000, 101 - 999)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Related product manuals