2.11 o: Keypad-Related Settings
448 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
Note:
Sets the number of the U monitor you will log.
For example, to show U1-01 [Frequency Reference], set o5-10 = 101. When it is not necessary to set data log monitors, set this parameter to
000. You cannot select U2 monitor [Fault Trace] or U3 Monitor [Fault History].
o5-11: Log Monitor Data 9
No.
(Hex.)
Name Description
Default
(Range)
o5-11
(155B)
RUN
Log Monitor Data 9
Sets the data log monitor. This parameter is only available with an LCD keypad.
000
(000, 101 - 999)
Note:
Sets the number of the U monitor you will log.
For example, to show U1-01 [Frequency Reference], set o5-11 = 101. When it is not necessary to set data log monitors, set this parameter to
000. You cannot select U2 monitor [Fault Trace] or U3 Monitor [Fault History].
o5-12: Log Monitor Data 10
No.
(Hex.)
Name Description
Default
(Range)
o5-12
(155C)
RUN
Log Monitor Data 10
Sets the data log monitor. This parameter is only available with an LCD keypad.
000
(000, 101 - 999)
Note:
Sets the number of the U monitor you will log.
For example, to show U1-01 [Frequency Reference], set o5-12 = 101. When it is not necessary to set data log monitors, set this parameter to
000. You cannot select U2 monitor [Fault Trace] or U3 Monitor [Fault History].
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV