5.3 Control Circuit Wiring
504 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
Table 5.1 Multi-function Input Terminals
Type Terminal Name (Default) Function (Signal Level)
MFDI
S1
MFDI selection 1
(ON: Forward run, OFF: Stop)
Photocoupler
24 V, 6 mA
Note:
To set the MFDI power supply (Sinking/Sourcing Mode or internal/
external power supply), install or remove a jumper between
terminals SC-SP or SC-SN depending on the application.
Sinking Mode, Internal power supply: Install the jumper to close
the circuit between terminals SC-SP.
NOTICE: Damage to Equipment. Do not close
the circuit between terminals SC-SN. If you
close the circuits between terminals SC-SP and
terminals SC-SN at the same time, it will cause
damage to the drive.
Sourcing Mode, Internal power supply: Install the jumper to close
the circuit between terminals SC-SN.
NOTICE: Damage to Equipment. Do not close
the circuit between terminals SC-SP. If you
close the circuits between terminals SC-SP and
terminals SC-SN at the same time, it will cause
damage to the drive.
External power supply: Remove the jumper from the MFDI
terminals. It is not necessary to close the circuit between terminals
SC-SP and terminals SC-SN.
S2
MFDI selection 2
(ON: Reverse run OFF: Stop)
S3
MFDI selection 3
(External fault (N.O.))
S4
MFDI selection 4
(Fault reset)
S5
MFDI selection 5
(Multi-step speed reference 1)
S6
MFDI selection 6
(Multi-step speed reference 2)
S7
MFDI selection 7
(Jog command)
SN MFDI power supply 0 V
MFDI power supply, 24 V (maximum 150 mA)
NOTICE: Damage to Equipment. Do not close the
circuit between terminals SP-SN. If you close the
circuits between terminals SC-SP and terminals
SC-SN at the same time, it will cause damage to
the drive.
SC MFDI selection common
SP MFDI power supply +24 Vdc
Safe Disable Input
H1 Safe Disable input 1
Remove the jumper between terminals H1-HC and H2-HC to use the
Safe Disable input.
24 V, 6 mA
ON: Normal operation
OFF: Coasting motor
Internal impedance 4.7
OFF Minimum OFF time of 3 ms.
H2 Safe Disable input 2
HC Safe Disable function common
Safe Disable function common
NOTICE: Do not close the circuit between
terminals HC and SN. A closed circuit between
these terminals will cause damage to the drive.
Master Frequency
Reference
RP
Master frequency reference pulse train input
(Master frequency reference)
Response frequency: 0 to 32 kHz
H level duty: 30% to 70%
H level voltage: 3.5 V to 13.2 V
L level voltage: 0.0 V to 0.8 V
Input impedance: 3
+V Power supply for frequency setting 10.5 V (allowable current 20 mA maximum)
A1
MFAI1
(Master frequency reference)
Voltage input
Use H3-01 [Terminal A1 Signal Level Select] to select the signal level.
0 V to 10 V/ 100% (input impedance: minimum 15 kΩ)
-10 V to +10 V/-100% to +100% (input impedance: minimum 15
kΩ)
A2
MFAI2
(Combined to terminal A1)
Voltage input or current input
Use DIP switch S1 and H3-09 [Terminal A2 Signal Level Select] to
select the input.
0 V to 10 V/ 100% (input impedance: minimum 15 kΩ)
-10 V to +10 V/-100% to +100% (input impedance: minimum 15
kΩ)
4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250
Ω)
AC Frequency reference common 0 V
Output Terminals
Refer to Table 5.2 and Table 5.3 for a list of Output terminals and functions.