1.9 F: Options
54 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
No.
(Hex.)
Name Description
Default
(Range)
F7-38
(037A)
Dynamic In Param 6 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the
MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive
returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and
the value sent to Input Assembly 166 is not defined.
0
F7-39
(037B)
Dynamic In Param 7 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the
MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive
returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and
the value sent to Input Assembly 166 is not defined.
0
F7-40
(037C)
Dynamic In Param 8 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the
MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive
returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and
the value sent to Input Assembly 166 is not defined.
0
F7-41
(037D)
Dynamic In Param 9 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the
MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive
returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and
the value sent to Input Assembly 166 is not defined.
0
F7-42
(037E)
Dynamic In Param 10 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the values from the
MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive
returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and
the value sent to Input Assembly 166 is not defined.
0
F7-60
(0780)
PZD1 Write (Control Word)
When you use a Profibus option, set the MEMOBUS/Modbus address for PZD1 (PPO output). PZD1
(PPO output) functions as the STW when F7-60 = 0 to 2.
0
F7-61
(0781)
PZD2 Write (Frequency
Reference)
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD2 (PPO output).
PZD2 (PPO output) functions as the HSW when F7-61 = 0 to 2.
0
F7-62
(0782)
PZD3 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD3 (PPO output). A
value of 0, 1, or 2 will disable the PZD3 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-63
(0783)
PZD4 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD4 (PPO output). A
value of 0, 1, or 2 will disable the PZD4 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-64
(0784)
PZD5 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD5 (PPO output). A
value of 0, 1, or 2 will disable the PZD5 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-65
(0785)
PZD6 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD6 (PPO output). A
value of 0, 1, or 2 will disable the PZD6 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-66
(0786)
PZD7 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD7 (PPO output). A
value of 0, 1, or 2 will disable the PZD7 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-67
(0787)
PZD8 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD8 (PPO output). A
value of 0, 1, or 2 will disable the PZD8 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-68
(0788)
PZD9 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD9 (PPO output). A
value of 0, 1, or 2 will disable the PZD9 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-69
(0789)
PZD10 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD10 (PPO output). A
value of 0, 1, or 2 will disable the PZD10 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
F7-70
(078A)
PZD1 Read (Status Word)
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD1 (PPO input). PZD1
(PPO input) functions as the ZSW when F7-70 = 0.
0
F7-71
(078B)
PZD2 Read (Output
Frequency)
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD2 (PPO input). PZD2
(PPO input) functions as the HIW when F7-71 = 0.
0
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV