Parameter List
1
1.11 L: Protection Functions
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 89
No.
(Hex.)
Name Description
Default
(Range)
L8-07
(04B3)
Output Phase Loss
Protection Sel
Sets the function to enable and disable output phase loss detection. The drive starts output phase loss
detection when the output current decreases to less than 5% of the drive rated current.
Note:
The drive can incorrectly start output phase loss detection in these conditions:
The motor rated current is very small compared to the drive rating.
The drive is operating a PM motor with a small load.
0 : Disabled
1 : Fault when one phase is lost
2 : Fault when two phases are lost
1
(0 - 2)
L8-09
(04B5)
Output Ground Fault
Detection
Sets the function to enable and disable ground fault protection.
0 : Disabled
1 : Enabled
Determined by o2-04
(0, 1)
L8-10
(04B6)
Heatsink Fan Operation
Selection
Sets operation of the heatsink cooling fan.
0 : During Run, w/ L8-11 Off-Delay
1 : Always On
2 : Temperature-Dependent Fan Ctrl.
0
(0 - 2)
L8-11
(04B7)
Heatsink Fan Off-Delay
Time
Sets the length of time that the drive will wait before it stops the cooling fan after it cancels the Run
command when L8-10 = 0 [Heatsink Fan Operation Selection = During Run, w/ L8-11 Off-Delay].
60 s
(0 - 300 s)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
Note:
The setting range changes when the L8-35 [Installation Method Selection] value changes:
0 [IP20/UL Open Type]: -10 °C to +60 °C
1 [Side-by-Side Mounting]: -10 °C to +50 °C
2 [IP20/UL Type 1]: -10 °C to +50 °C
3 [External Heatsink/Finless]: -10 °C to +50 °C
40 °C
(-10 °C - +60 °C)
L8-15
(04BB)
Drive oL2 @ Low Speed
Protection
Sets the function to decrease the drive overload level at which the drive will trigger oL2 [Drive
Overload] during low speed operation (6 Hz or slower) to prevent damage to the main circuit
transistors.
Note:
Contact Yaskawa or your nearest sales representative before disabling this function at low
speeds. If you frequently operate drives with high output current in low speed ranges, it can cause
heat stress and decrease the life span of drive IGBTs.
0 : Disabled (No Additional Derate)
1 : Enabled (Reduced oL2 Level)
1
(0, 1)
L8-18
(04BE)
Software Current Limit
Selection
Set the software current limit selection function to prevent damage to the main circuit transistor
caused by too much current.
0 : Disabled
1 : Enabled
0
(0, 1)
L8-19
(04BF)
Freq Reduction @ oH Pre-
Alarm
Sets the ratio at which the drive derates the frequency reference during an oH alarm.
0.8
(0.1 - 0.9)
L8-27
(04DD)
Overcurrent Detection Gain
Sets the PM motor overcurrent detection level as a percentage of the motor rated current value.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor rated current.
A1-02 8[EZOLV]: E5-03 [PM Motor Rated Current (FLA)]
A1-02 = 8: E9-06 [Motor Rated Current (FLA)]
300.0%
(0.0 - 1000.0%)
L8-29
(04DF)
Output Unbalance Detection
Sel
Sets the function to detect LF2 [Output Current Imbalance].
0 : Disabled
1 : Enabled
1
(0, 1)
L8-31
(04E1)
LF2 Detection Time
Sets the LF2 [Output Current Imbalance] detection time.
3
(1 100)
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV